Water cassette fan coil unit (E) with pump 

Water cassette type fan coil unit (E) passed ISO 9001 and CE certificate, we offer 18 months warranty. 

We supply four way cassette fan coil unit which passed ISO 9001 and CE certificate. The unit has 18 months warranty. Our companies focus on fan coil unit producing for 10 years. We are expecting become your long-term partner in China.


Product introduction of water cassette fan coil unit (E) with pump.

MECO’s cassette type fan coil unit is developed by long time producing and selling experience. As a complex product in this field, cassette type fan coil unit is always a hard point for many manufactories. The E style cassette fan coil unit makes installation easier. It can adapt to a variety of complex installation environment. The M style cassette fan coil unit is our core competitiveness which has high stability and comprehensive function.


Products specification of water cassette fan coil unit (E) with pump.

PERFORMANCE OF CASSETTE TYPE FAN COIL(4-WAY,2 TUBE)---DRAINED BY  WATER PUMP
model MFP-34KM-(Q)EE1 MFP-51KM-(Q)EE1 MFP-68KM-(Q)EE1 MFP-85KM-(Q)EE2 MFP-102KM-(Q)EE2 MFP-136KM-(Q)EE2 MFP-136KM-(Q)EE3 MFP-170KM-(Q)EE3 MFP-204KM-(Q)EE3 MFP-238KM-(Q)EE3
model MFP-34KM-(Q)E1 MFP-51KM-(Q)E1 MFP-68KM-(Q)E1 MFP-85KM-(Q)E2 MFP-102KM-(Q)E2 MFP-136KM-(Q)E2 MFP-136KM-(Q)E3 MFP-170KM-(Q)E3 MFP-204KM-(Q)E3 MFP-238KM-(Q)E3
model of panel MB-SB01E1 MB-SB01E2 MB-SB01E3
power supply 220V,50Hz,1Ph
air volume H m3/h 340 510 680 850 1020 1300 1360 1700 2040 2380
M 280 380 515 660 765 1000 1040 1280 1550 1800
L 180 260 340 430 530 680 710 860 1050 1280
static pressure Pa 0 0 0 0 0 0 0 0 0 0
cooling capacity TH H W 1800 2700 3600 4500 5400 7000 7200 9000 10800 12600
BTU/h 6142 9212 12283 15354 18425 23884 24566 30708 36850 42991
SH W 1311 1971 2700 3184 4196 5158 5362 6707 8072 9070
BTU/h 4473 6725 9212 10864 14317 17599 18295 22884 27542 30947
TH M W 1500 2460 3000 3715 4423 6289 6435 7848 9296 10500
SH W 994 1555 1995 2426 3041 4156 4236 5393 6603 7190
TH L W 1391 2057 2479 2921 3793 5478 5604 7223 8534 8900
SH W 823 1200 1530 1826 2373 3196 3284 4416 5248 5500
heating capacity H W 2700 4050 5400 6750 8100 10500 10800 13500 16200 18900
M W 1949 2770 3938 4902 5694 7687 7924 10473 12997 13900
L W 1297 1774 2779 3505 3876 5342 5421 6992 8645 9700
noise H 0Pa dB(A) 37 39 41 43 45 47 46 48 50 51
power input H 0Pa W 37 52 62 76 96 125 134 152 189 228
waterflow volume m3/h 0.31 0.46 0.62 0.77 0.93 1.23 1.23 1.54 1.85 2.16
water pressure dropping kPa 11.8 11.8 22.4 27 29.6 29.6 29.6 35.4 35.4 40
dimension of water(in & out)connection pipe in ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4"
out ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4"